To view this page ensure that Adobe Flash Player version 11.1.0 or greater is installed.
COMMERCIAL FEATURE
Safe testing
of circuit breakers
By Nils Wacklen – product manager, circuit breaker testing, Megger Sweden
A fter long periods of inactivity,
a circuit breaker must function
perfectly when needed. The best
opportunity to test for this is the first-trip
test. The rated operating sequence (also
known as the standard operating duty
or standard duty cycle) is the specified
operating sequence that the circuit
breaker must be able to perform at
specified ratings. Breaker manufacturers
normally specify these sequences and
corresponding rated times, which are
defined in IEC 62271-100.
Many regulations and laws require
all electrical equipment to be grounded
on both sides before any maintenance
work is carried out. During circuit
breaker maintenance, however, the
most basic and important test – main
contact timing – is usually performed
without this basic safety prerequisite.
The reason is simple; conventional
technology does not offer a safe way
of carrying out timing tests on circuit
breakers. Now, however, DualGround/
DCM technology offers a much safer
approach to testing.
First introduced in 2006, this
novel testing technique offers greatly
increased safety for personnel, and is
suitable for use with circuit breakers of
all types. It is non-intrusive and does
not require any special preparatory
information. Despite these benefits,
the basic method of working and
the interpretation of results remain
unchanged, except that testing is much
faster and easier.
With DualGround testing, it is
possible to carry out timing tests on the
main contacts of a circuit breaker
while both sides of the breaker are
grounded. This means that personnel
can be kept at a safe distance from
dangerous voltages – a safe area can
be created around the circuit breaker
under test and clearly marked with
security fencing.
Even though safety protocols
dictate that both sides of a breaker
should be grounded during field tests,
conventional timing methods require the
110 ground to be lifted on one side of the
breaker to allow for the test instrument
to sense the change in contact status.
This means that the test cables and the
instrument form a path for capacitive
coupled current while the test is being
performed. In contrast, the DualGround
method allows reliable measurements
to be made while both sides of the
circuit breaker are grounded, which
makes the test faster and easier. The
DualGround technique also makes it
possible to test circuit breakers in gas
insulated switchgear (GIS), generator
and transformer applications where
conventional timing methods require
the removal of jumpers and busbar
connections. Timing measurements are difficult to
make with both sides of a circuit breaker
grounded. However, the DualGround
or dynamic capacitance measurement
(DCM) method of timing gives accurate
and dependable results, even when the
ground resistance is low. There is no
lower limit on ground loop resistance;
even if the ground loop has a lower
resistance than the main contact/arcing
contact path, the method still works.
This is particularly important when
testing GIS breakers and generator
breakers, and is also relevant for air
insulated switchgear breakers that have
fairly low resistive grounding appliances,
say a couple of milliohms.
The reason for the superiority of
the DualGround/DCM test technology
is that it uses a high frequency to
achieve resonance in the test circuit.
The resonant frequency varies when
the circuit breaker changes state, and
this variation can easily be used to
determine when the contacts close and
open. There are other technologies that
use dynamic resistance measurement
(DRM) to time circuit breakers with both
sides grounded. A current is injected
and the voltage drop across the circuit
breaker is recorded, allowing the
resistance to be calculated. The breaker
state is determined by evaluating the
resistance graph against an adjustable
threshold. If the resistance is below the
threshold, the breaker is considered
closed and if it is above the threshold
the breaker is considered open.
Difficulties arise when it comes to
setting this threshold since it has to
be below the ground loop resistance
(which is initially unknown) but above
the resulting resistance of the arcing
contact (which also is unknown) and the
ground loop in parallel. This is because,
according to the IEC standard, it is the
closing/opening of the arcing contact
that determines the breaker’s operation
time, not the closing/opening of the
main contact. The difference between
main and arcing contact operation time
can, depending on contact speed, be as
much as 10 ms.
Further, a 95 mm2 copper
grounding cable of length 2.0 x 10 m has
a resistance of about 3.6 mΩ, neglecting
connection resistances. Arcing contacts
also usually have resistance ranging
from a couple of milliohms up to about
10 mΩ depending on the type of breaker
and the condition of the arcing contact.
Taken together, these factors make
setting the thresholds for DRM testing
an almost arbitrary task.
When both sides of a circuit breaker
are grounded, a loop is formed with
a large area exposed to the magnetic
fields from surrounding live conductors.
These fields induce a current, which
can be as large as tens of amps, in the
circuit breaker/grounding loop. This is
a very significant proportion of a test
current of, say, 100 A. If the evaluation
threshold is close to the limit, such an
induced current would definitely impair
the accuracy of the timing results.
In contrast, the DualGround/DCM
method for contact timing is completely
unaffected by 50/60 Hz induced currents
and interference. ESI
This article is an extract from
The Circuit Breaker Testing Guide
available at www.megger.com
ESI AFRICA ISSUE 1 2014